Design of Six Pulse Bridge Multiplication Converter Model for Current Harmonic Elimination of Three Phase AC-DC Converter

Keywords: Total Harmonic Distortion, Harmonic Mitigation, Six Pulse Bridge Multiplication Converter, Shunt Harmonic Passive Filter, Power Quality Analyzer

Mehran University Research Journal of Engineering & Technology

Volume 33 ,  Issue 4

MANSOOR AHMED   SOOMRO,IRFAN AHMED HELEPOTO  ,ANWAR ALI SAHITO  

Abstract

The recent development of semiconductor technology and wide spread use of power electronic devices in power system have open the era of the power system harmonics due to increasing penetration of non-linear loads. Harmonics are widely admitted as most important issues of power quality which must be eliminated to maintain power system reliability. The tolerable THD (Total Harmonic Distortion) values must be bounded in well-defined limits recognized by IEEE-519 standard. In this work, in order to eliminate the current harmonics produced by non-linear loads, six pulse multiplication converter technique in conjunction with STSSHPE (Single Tuned Shunt Harmonic Passive Filter) is proposed. The proposed model has the capacity of harmonic cancellation of the dominant 3rd order harmonics. Besides that, the 5th and 7th order harmonics are also reduced to a diminishing level. The hardware model has been experimentally tested by PQA (Power Quality Analyzer) and simulation model is designed using MATLAB software. The acquired results have been measured by considering THD values in terms of current and voltage. Furthermore, they have been compared against IEEE-519 performance standards. The prosed model, successfully bounds the total harmonic distortion under defined limits by IEEE-519 standard